nav

Hunan Kare Air Conditioning Co., Ltd.  湘ICP备14005289号  www.300.cn

Three Cascade low temperature chiller

Three Cascade low temperature chiller

basic information
Categories:
Superimposed cryogenic refrigerator
heat
没有此类产品
Describe
Three Cascade low temperature chiller Technical parameters
Model No. of KARE

KRT9LT

(FD)

KRT12LT

(FD)

KRT13LT

(FD)

KRT15LT

(FD)

KRS25LT

(FD)

KRS35LT

(FD)

KRS45LT

(FD)

KRS50LT

(FD)

KRS60LT

(FD)

KRS66LT

(FD)

KRS78LT

(FD)

KRS82LT

(FD)

Rated

Cooling

Capacity

-105~-

110℃

KW 8.7 11.8 13 14.9 25 34.2 45.1 49.1 59.8 65.8 77.8 82.3
Power supply - 3Φ-380V-50Hz
Input Power KW 41 54 60 85 120 145 180 205 220 240 290 320

First

step

Compressor

Power KW 10.5 11.2 13.4 31.6 36.9 41.1 54.6 62.5 65.9 72.3 90.6 101.9
Refrigerant - R404A

Starting

mode

-

Part of the

coil start

Y-△

Second

step

Compressor

Power KW 7.4 8.6 9.5 13.2 17.4 21.8 29.1 31.7 35.7 37.6 45.1 50.2
Refrigerant - R23

Starting

mode

- Part of the coil start Y-△          

Third

step

Compressor

Power KW 6.5 8.7 9.9 11.5 25 27.5 34.5 37.8 46 50.1 56.4 59.4
Refrigerant - R14

Starting

mode

- Part of the coil start Y-△

Condensor

Evaporator

Type - Plate heat exchanger

Evaporator
Type - Plate heat exchanger
Capacity

m3

/h

3.7 5.1 5.6 6.4 10.7 14.7 19.3 21 25.6 28.2 33.3 35.3
Condensor Type -  Shell&tube heat exchanger

Water

flow

m3

/h

5.7 6.9 7.9 12.2 17.9 21.4 28 31 35.6 38.7 45.5 50.4

Joint

pipe

diameter

Evaporator mm DN40 DN40 DN40 DN40 DN50 DN50 DN50 DN65 DN65 DN80 DN80 DN80
Condensor mm DN40 DN40 DN40 DN50 DN50 DN65 DN65 DN80 DN80 DN80 DN80 DN80

Dimensions
(L) mm 2300 2500 2700 2900 3100 3300 3700 3900 4100 4100 4400 4500
(W) mm 1100 1100 1200 1200 1300 1300 1500 1600 1600 1600 1700 1900
(H) mm 1650 1700 1700 1750 1750 1800 1900 1900 2000 2000 2100 2200
 Weight (Dry) KG 1279 1548 1945 2492 2734 3352 4829 5116 5204 5294 6086 6836
(Wet) KG 1407 1703 2139 2741 3008 3687 5312 5627 5724 5821 6694 7519
 
RE:
1.Cooling Conditions for above refrigerating capacity: Refrigerating medium is alcohol, cooling water inlet 32℃, outlet 37℃. 
2.Cooling range: Chilled water outlet temperature 22℃~37℃, inlet temperature difference 3.5℃~10℃. Refrigerating fluid outlet temperature -75℃~-115℃, inlet temperature difference 2.5℃~10℃.
3.With pairing connecting flange for inlet and outlet of cooling water and refrigerating fluid. The refrigerating medium(alcohol) equipped by user.
4.The above specification will change due to product improvement, without prior notice. Please contact us before order if you have special requirements.
On a
Two Cascade low temperature chiller